Cable + Wire Identification Reference

Why this matters

A walk through any panel or junction box shows cables labeled by code (NM-B 14/2, THHN/THWN-2, MC, BX) + size. Knowing which is which determines safety, ampacity, install location compatibility, and code compliance. The tech who reads cable markings fluently avoids using the wrong cable for the application + flags unsafe situations. This is the field card.

Cable markings on the jacket

Manufacturers print key info every few feet along the cable jacket. Look for:

  • Conductor count + size: e.g., "14/2 W/G" = 14 AWG, 2 conductors + ground
  • Cable type: NM-B, NMC-B, UF-B, THHN, MC, AC, etc.
  • Voltage rating: 600V (common), 300V (some)
  • Manufacturer + part number
  • UL listing
  • Temperature rating: 60°C, 75°C, 90°C
  • Material: copper (CU) OR aluminum (AL)
  • Year of manufacture: sometimes present

Read the markings before disconnecting / reconnecting anything. The cable's specs determine acceptable use.

NM-B (Romex)

Non-metallic sheathed cable, 90°C: the most common residential branch wiring.

  • White jacket: 14 AWG (15A circuits)
  • Yellow jacket: 12 AWG (20A circuits)
  • Orange jacket: 10 AWG (30A circuits)
  • Black jacket: 8 AWG and 6 AWG (40A, 50A circuits)
  • Gray jacket: 4 AWG and larger

Inside the jacket: 2 OR 3 insulated conductors + bare grounding conductor.

Color-coded jacket is post-2001 (NEC change); older cable is all-white regardless of size - look for the AWG marking on the jacket.

Use: dry interior locations behind drywall, in framed walls, exposed in unfinished basements (where allowed by code).

Don't use: outdoors, in conduit underground, in damp/wet locations, embedded in concrete.

NMC-B (corrosion-resistant Romex)

Similar to NM-B but rated for damp locations. Less common; specific applications.

UF-B (Underground Feeder)

Direct-burial cable. Solid jacket extruded around the conductors (not just a sheath like NM-B).

Use: outdoor direct burial, wet locations, exterior applications.

Identification: gray jacket typically; thicker than NM-B for same size; "UF-B" marking.

THHN / THWN

Individual conductors, not a multi-conductor cable. Each wire has its own colored insulation, used together in conduit.

  • THHN: 90°C, dry locations only
  • THWN: 75°C, wet locations OK
  • THHN-2: 90°C in dry + wet (modern standard, often dual-rated as THHN/THWN-2)

Use: pulled through conduit (EMT, IMC, PVC, flex). Common for industrial + commercial + residential where conduit is required.

Identification: single conductor in colored insulation (no outer jacket); markings on the insulation itself.

MC (Metal-Clad Cable)

Flexible metal jacket containing color-coded THHN-style conductors.

Use: where NM-B isn't allowed (some commercial, some plenum spaces), where physical protection is needed.

Identification: spiral metal armor on the outside; visible metallic appearance.

AC (Armored Cable, "BX")

Predecessor to MC. Spiral metal armor + paper-wrapped conductors. Older homes have this; rarely installed new.

Identification: similar appearance to MC but older; check markings.

SE (Service Entrance)

Heavy cable from meter to main panel. Multiple variations:

  • SEU: service entrance, unarmored
  • SER: service entrance, round
  • USE: underground service entrance

Use: service entrance + feeder applications.

Identification: large diameter; multiple thick conductors; specific markings.

Low-voltage cable (Class 2 / 3)

Per NEC 725. Examples:

  • Bell wire (18 - 22 AWG): doorbell, HVAC thermostat, alarm
  • CAT5e / CAT6: ethernet, communications
  • Speaker wire: 14 - 18 AWG
  • Coaxial (RG-6): TV, antenna, satellite

Identification: smaller diameter; specific application markings (CAT5e, RG-6); typically labeled.

Plenum-rated cable

Used in air-handling spaces (plenums, return-air spaces). Special low-smoke, low-toxin insulation.

Identification: "CMP" (communications, plenum), "OFNP" (optical fiber, plenum), etc.

Use: required in dropped-ceiling returns, attic plenums, mechanical chases used as air ducts. Standard cable in plenum = code violation + fire risk.

Riser-rated cable

Used between floors of buildings (less stringent than plenum). "CMR" "OFNR" markings.

Old + legacy cable types

Knob + tube wiring (pre-1940): separate hot + neutral conductors run on porcelain insulators. Not grounded. Insurance + code issues; rewire recommended.

Cloth-jacketed BX (1940s - 1950s): armored cable with cloth-insulated conductors; brittle.

Cloth-jacketed NM (early Romex predecessors): cloth + rubber insulation; brittle after decades.

Aluminum branch wiring (1965 - 1973): silver-colored aluminum conductors in NM-B-style cable; CO/ALR-rated devices required.

Federal Pacific cables: not specifically the cable but the panel - Federal Pacific Stab-Lok panels have known reliability problems.

Recognizing these alerts you to insurance, code, + safety considerations.

Conductor identification (color inside cable)

NM-B inside the jacket:

  • Black: hot (line) - primary hot
  • White: neutral
  • Red: second hot (3-conductor cable)
  • Blue / yellow: in 4-conductor + multi-conductor; per code or designer convention
  • Bare or green: equipment grounding conductor

In THHN/THWN through conduit, each conductor is its own color per code conventions. See wiring color codes.

Cable sizing for ampacity

Per NEC Table 310.16 (75°C copper):

  • 14 AWG = 15A (NM-B)
  • 12 AWG = 20A (NM-B + THHN)
  • 10 AWG = 30A
  • 8 AWG = 50A
  • 6 AWG = 65A
  • 4 AWG = 85A
  • 2 AWG = 115A
  • 1 AWG = 130A
  • 1/0 AWG = 150A
  • 2/0 AWG = 175A
  • 3/0 AWG = 200A
  • 4/0 AWG = 230A

Aluminum conductors are sized larger for the same ampacity (rough rule: aluminum needs 2 sizes larger than copper for equivalent current).

Derating applies for ambient temperature + multiple conductors in conduit + cable type. See NEC for full tables.

Identifying mystery cable in older homes

Walk through an older home, see cable you can't identify:

  1. Look for jacket markings (may be faded; clean carefully with damp cloth)
  2. Note the conductor count + sizes
  3. Compare to known cable types
  4. Photograph for reference / sharing with senior tech
  5. Look up similar cable images online if unsure

When in doubt + cable supports a circuit, treat it as suspect (could be undersized OR wrong-rated for application) + recommend electrician evaluation.

Common service issues + cable

Customer DIY work using NM-B outdoors / in conduit: code violation; replace with proper cable.

References

  • NEC Article 310 (Conductors for General Wiring)
  • NEC Article 334 (Nonmetallic-Sheathed Cable Type NM)
  • NEC Article 338 (Service-Entrance Cable Types SE + USE)
  • NEC Tables 310.15(B) and 310.16 (ampacity)
  • UL 83, UL 1581 (cable standards)
  • Manufacturer technical data (Southwire, Encore, Cerrowire)
  • Manuall internal: Wiring Color Codes, Wire Termination Types, Electrical Box Sizing