Wire Color Code Reference

Overview

NEC-compliant wire color identification for residential and light-commercial systems. Quick-reference for techs who work across both new construction (clean color discipline) and renovation (where prior owners' "creative" wiring undermines every color assumption). Mis-identifying a conductor causes shock injuries and equipment damage - when in doubt, verify with a meter, never assume from color.

Reference Table

Single-phase 120/240 V (standard residential)

Conductor Color Notes
Hot (line 1) Black Common general-purpose hot
Hot (line 2) Red Second hot leg on 240 V circuits, or switch leg
Hot (additional) Blue Used as switch traveler or third hot
Neutral (grounded) White or gray Carries return current at zero potential
Equipment ground Bare copper or green Bonded to panel ground bus
Switch leg (re-marked) Often white with black tape Older code; flag any white wire feeding a switch loop

Three-phase 120/208 V (light commercial)

Conductor Color Notes
Phase A Black
Phase B Red
Phase C Blue
Neutral White or gray
Equipment ground Green or bare

Three-phase 277/480 V (commercial)

Conductor Color Notes
Phase A Brown
Phase B Orange High leg on 240 V high-leg deltas (per NEC 110.15)
Phase C Yellow
Neutral Gray
Equipment ground Green

Low-voltage (24 V controls, doorbells, thermostats)

Conductor Color Notes
Red Power (R or RH on thermostats)
White Heat call (W)
Yellow Cooling call (Y)
Green Fan call (G)
Blue or black Common (C)
Orange / Brown Reversing valve (O or B) on heat pumps

Notes

  • Re-marked white wires: NEC permits identifying a white wire as a hot conductor by wrapping it with electrical tape (black or red) - but ONLY in cable assemblies (Romex / NM-B) where you can't easily swap conductor colors. Loose-conductor circuits should never have a re-marked white. If you see one in a junction box, treat the entire installation with suspicion and verify every other conductor with a meter.
  • Orange "high leg": In old 240 V high-leg delta systems (rare but still in service in some industrial-zoned homes), phase B is the "wild" leg at 208 V to ground. Treating this as a normal 120 V circuit will destroy whatever you plug into it.
  • Aluminum branch wiring (1965 - 1973) uses the same color code but the wire is silver instead of copper. Aluminum-to-copper connections require COPALUM or AlumiConn connectors per NEC; standard wire nuts are a fire hazard.
  • Knob-and-tube (pre-1950) often has cloth-insulated wires with no color discipline. Verify every conductor; replace whenever the wire is exposed during other work.

Color is a clue, not a guarantee. Always verify with a meter before contact, especially on renovation work. The DIY homeowner who wired a sub-panel "right" by their own logic has caused more electrician injuries than every utility lineman job combined.

References

  • NEC Article 200.6 (Identification of Grounded Conductors)
  • NEC Article 200.7 (Use of Grounded Conductor)
  • NEC Article 210.5 (Identification of Branch Circuits)
  • NEC Article 250.119 (Identification of Equipment Grounding Conductors)