Furnace Ignition Systems Diagnosis Reference

Why this matters

Without ignition, the gas valve never opens. The furnace ignition system has evolved through three generations - standing pilot (pre-1990), intermittent pilot / spark (1990-2000), and hot-surface igniter (2000+) - and each has its own failure modes and diagnostic approach. Diagnosing the right one in the first 5 minutes makes the difference between a same-day fix and a return trip.

The three ignition types

Standing pilot (oldest, increasingly rare):

  • Small flame burning continuously
  • Thermocouple senses the flame; if flame fails, thermocouple cools, gas valve safety closes
  • Usually found on 80% AFUE units pre-1990
  • Failure: pilot extinguished (drafts, dirty orifice, weak thermocouple)
  • Diagnosis: relight pilot, replace thermocouple (inexpensive part) if it won't stay lit

Intermittent pilot (IPI) / spark ignition:

  • Pilot lights only when there's a heat call
  • High-voltage spark ignites the pilot, pilot ignites the main burner
  • Thermocouple or flame rod proves pilot
  • 1990s-2000s 80% AFUE furnaces
  • Failure: spark electrode fouled / cracked, pilot orifice plugged, ignition module failed
  • Diagnosis: visual spark, clean electrode, test for spark gap (1/8" typical)

Hot Surface Igniter (HSI):

  • High-resistance ceramic igniter heats to 1800-2400 °F
  • Direct ignition of main burner (no pilot)
  • 2000+ furnaces (80% and 90%+ AFUE)
  • Two material types:
    • Silicon carbide (SiC): older, fragile (the original HSI; cracks with thermal cycling)
    • Silicon nitride (Si3N4): modern, much more durable, lasts 15-20+ years vs 3-7 for SiC
  • Failure: cracked igniter (most common), igniter open circuit (winding burned out), wrong-voltage igniter installed
  • Diagnosis: ohms test cold, visual inspection

How a hot surface ignition sequence works

  1. Thermostat W terminal calls for heat
  2. Board energizes inducer; pressure switch closes
  3. Board energizes igniter (120 V AC applied)
  4. Igniter heats: visible orange glow within 30-60 seconds
  5. Board opens gas valve (with igniter still energized)
  6. Gas flows past glowing igniter; combustion starts
  7. Flame sensor proves flame (microamps); board latches gas valve open
  8. Board drops igniter (no longer needed)
  9. Blower delay timer starts
  10. After ~30-60 sec, blower energizes

If the igniter doesn't glow: open winding, board not sending voltage, wiring break. If it glows but burner doesn't light: gas valve issue, no gas, orifice plugged.

Hot Surface Igniter testing

Visual:

  • Look at the igniter through the burner-compartment sight glass during a heat call
  • Glowing orange within 30-60 seconds = working
  • Glowing red and white (very bright orange) = igniter at full temp
  • No glow at all = open winding OR no voltage

Cold ohm test (power off):

  • Disconnect igniter wiring at the connector
  • Meter on resistance (Ω) scale
  • Read across the two igniter leads
  • SiC igniter: typically 11-25 Ω cold (varies by manufacturer)
  • Si3N4 igniter: typically 40-80 Ω cold (varies)
  • Reading: OL (open): igniter winding broken - replace
  • Reading: 0 or near 0: shorted - replace
  • Reading: within spec: igniter is electrically OK; problem is upstream

Voltage test at the igniter (power on, during ignition trial):

  • Disconnect igniter leads
  • Meter on V AC, leads to the igniter wires at the harness end
  • During ignition trial, should read 120 V AC for ~10-30 seconds
  • No voltage = board not sending power → board issue OR safety circuit issue

Spark ignition (older furnaces) testing

Visual:

  • Look at the spark electrode during ignition trial
  • Should produce strong, bright blue-white spark across the gap (typically 1/8" / 3 mm)
  • Yellow / weak spark = high resistance, wet electrode, fouled
  • No spark = ignition module issue or wire to electrode

Spark voltage:

  • Ignition module produces 10-25 kV for the spark
  • Don't try to measure with a regular meter (will damage the meter)
  • Verify the cable is intact (no cracks in the silicone-rubber insulation)
  • Cracked cable arcs to ground before reaching electrode = no spark at burner

Standing pilot testing

Pilot flame check:

  • Pilot should be bluish with yellow tip, 3/4" to 1" tall, engulfing the thermocouple tip
  • Yellow / sooty / lazy: dirty orifice, blocked air shutter
  • Won't stay lit after holding pilot button: thermocouple weak/failed

Thermocouple test:

  • Disconnect thermocouple from gas valve
  • Light pilot; hold lit for 30 sec
  • Meter on DC millivolts (mV); connect across thermocouple's outer threaded shaft and the inner tip
  • Healthy thermocouple: 20-30 mV DC
  • Below 12-15 mV: replace

Common failure modes

HSI cracked / open:

  • Most common HSI failure
  • Often heard before seen: heat cycling causes the ceramic to crack; eventually the crack opens and the winding breaks
  • Replacement: modest-cost part, OEM (Si3N4) or aftermarket
  • 5-15 min labor

HSI degraded (resistance climbed):

  • Older SiC igniters can degrade gradually; resistance creeps up
  • Symptom: glow gets dimmer over years; eventually doesn't reach light-off temp
  • Replace at PM when resistance is borderline

Spark electrode fouled:

  • Carbon buildup on electrode = high resistance = weak spark
  • Clean with Scotch-Brite or 0000 steel wool (same as flame sensor)
  • Check gap with feeler gauge - typical 1/8"

Pilot orifice plugged (standing pilot):

  • Dust, debris, spider webs
  • Clean with compressed air or pipe cleaner (don't push debris further in)
  • Sometimes orifice needs replacement

Ignition module failed:

  • IPI / spark systems
  • Symptom: no spark even with verified power
  • Replace module

Gas valve sticky / failed:

  • Igniter glows but burner doesn't light
  • Verify gas is on at the valve handle
  • Listen for the click of the valve solenoid when board calls
  • 24V test at the valve coil terminals

Diagnostic procedure

  1. Read the board's LED code first. Most boards report "ignition failed" with a specific flash code.
  2. Visual check during ignition trial:
  • HSI: glows? Yes → next step. No → ohms test cold, voltage test at harness.
  • Spark: sparks across gap? Yes → next step. No → check module, electrode, cable.
  1. If ignition source works but burner doesn't light:
  • Verify gas valve handle is ON
  • Verify gas line pressure (manometer at the manifold tap, ~3.5" w.c. natural gas typical)
  • Listen for gas valve click
  1. If burner lights but board doesn't see flame:
  • See Flame Sensor Diagnosis and Cleaning Reference
  1. Document the trial sequence - when does it fail, in what step? That narrows the diagnosis.

Replacement procedure (HSI)

References

  • ANSI Z21.47 (Gas-Fired Central Furnaces)
  • Manufacturer service manuals (Carrier, Trane, Lennox, Goodman, Rheem) - for igniter resistance specs and replacement part numbers
  • NATE / RSES training on ignition systems
  • Manuall internal: Furnace Pressure Switch Diagnosis, Flame Sensor Diagnosis and Cleaning, Furnace Control Board Diagnosis