Chiller Systems (Commercial) Reference
Why this matters
Commercial chillers are central air conditioning's bigger sibling - instead of cooling air directly, they cool water (chilled water at 42-45 °F supply) that's then circulated to air handlers throughout the building. They scale from 10 tons (small office) to 1000+ tons (high-rise). The diagnostic approach differs from split residential systems - chillers have more sub-systems (chilled water loop, condenser water loop, refrigerant circuit, controls, often multiple compressors), and a chiller failure can shut down an entire building's cooling.
Chiller architecture
Refrigerant circuit:
- Compressor (centrifugal / screw / scroll / reciprocating, varies by tonnage)
- Condenser (water-cooled or air-cooled)
- Expansion valve (TXV or EEV)
- Evaporator (cools the chilled water loop)
Chilled water loop:
- Pumps circulate water through evaporator (where it's cooled)
- Distributed to AHUs (air handler units) throughout the building
- Returns warm to the chiller for re-cooling
Condenser water loop (water-cooled chillers only):
- Pumps circulate water through condenser (where it picks up heat)
- Routed to cooling tower (rejects heat to atmosphere via evaporation)
- Returns to condenser
Air-cooled chillers skip the water condenser; instead, large condenser coils with fans reject heat directly to outdoor air. Simpler but less efficient and noisier.
Compressor types by tonnage
| Type | Tonnage range | Characteristics |
|---|---|---|
| Reciprocating | 5-200 tons | Older, fewer in service; multiple cylinders; loud |
| Scroll | 10-200 tons | Quiet, reliable, smaller commercial; common in mid-sized buildings |
| Screw | 50-500+ tons | Twin-rotor compression; efficient at part-load; common large commercial |
| Centrifugal | 200-2000+ tons | Most efficient at full load; large building / chiller plants; impeller-based |
| Variable-speed inverter | scaled | Modern efficiency boost; magnetic bearings on premium units |
Key performance metrics
- Tonnage: 1 ton of cooling = 12,000 BTU/hr (the energy to melt 1 ton of ice in 24 hours)
- kW/ton: electrical input per ton of cooling. Lower is better. Modern chillers: 0.45-0.55 kW/ton at full load; 0.35-0.50 at part-load IPLV.
- IPLV (Integrated Part-Load Value): weighted-average efficiency across load profile; meaningful for buildings that run mostly part-load.
- COP (Coefficient of Performance): cooling out / electricity in. Modern chillers: 5-7+ at full load.
- ΔT chilled water: typical 10-12 °F (55 °F return - 44 °F supply, for example)
- ΔT condenser water: typical 10 °F (85 °F supply - 95 °F return, for example)
Refrigerants in chillers
- R-134a: common in centrifugal chillers; being phased down under HFC regulations
- R-1234ze, R-513A: low-GWP replacements becoming common
- R-410A: scroll chillers, packaged units
- R-32: newer scroll units
- Ammonia (R-717): industrial / very large; not residential
- Always check the refrigerant type before service; EPA Section 608 cert required
Common failure modes
Chiller won't start / locks out on safety:
- Low chilled-water flow → flow switch open
- High discharge pressure (condenser water issue, cooling tower problem, refrigerant overcharge)
- Low suction pressure (refrigerant undercharge, low chilled-water temperature)
- Compressor overload
- Microprocessor fault (read fault codes)
Chiller runs but doesn't cool to setpoint:
- Refrigerant low → recover, leak-check, recharge
- Condenser tubes scaled / dirty → reduced heat rejection → high discharge
- Evaporator tubes scaled / dirty → reduced heat absorption → low chilled-water capacity
- Compressor mechanical degradation → low compression ratio
- Excess load → building demand exceeds chiller capacity
Chiller cycles rapidly:
- Chilled water flow inadequate (short cycling on flow switch)
- Setpoint too tight
- Pump issues
Cooling tower issues (water-cooled):
- Fan failure → no heat rejection
- Spray nozzles plugged → low water flow over fill
- Bleed-off valve clogged → high TDS in water → scale formation
- Belt drive worn → fan slow
Maintenance schedules (industry-standard)
Daily / weekly:
- Read pressures, temperatures, water flows
- Log chiller status
- Check cooling tower water quality (TDS, pH)
- Verify normal operation
Monthly:
- Clean cooling tower strainer
- Check chilled water and condenser water pH, biocide levels
- Inspect for visible leaks
- Verify control sequence
Quarterly:
- Check refrigerant charge (subcool / superheat) - see Superheat Subcooling Method Reference
- Test safety controls (high-pressure cutout, low-pressure cutout, freeze stat)
- Inspect electrical connections in starter
Annually:
- Eddy-current testing of chiller tubes (every 3-5 years)
- Condenser water chemistry full analysis
- Refrigerant leak test (per EPA 608)
- Compressor oil analysis
- Bearing lubrication / replacement per manufacturer
Water quality (water-cooled chillers)
Cooling tower water is exposed to air and concentrates impurities as water evaporates. Without treatment:
- Scale formation: calcium carbonate deposits on condenser tubes; thermal resistance climbs; chiller efficiency drops
- Biological growth: algae, bacteria (including Legionella) thrive in warm, oxygenated water
- Corrosion: dissolved oxygen + dissolved minerals attack metal components
Treatment program:
- Conductivity-based bleed-off (controls TDS / cycles of concentration; typical 3-5 cycles)
- Corrosion inhibitor
- Scale inhibitor / dispersant
- Biocide (oxidizing + non-oxidizing rotation)
- Routine testing (weekly or biweekly)
- Annual Legionella testing per ASHRAE 188 in some applications
Brand-specific notes
- Trane CenTraVac (centrifugal): premium, common large commercial; Magnetic Bearing chillers (no oil) on newer Series E units
- Carrier 19XR / 23XR (centrifugal): premium large
- York Millennium / OptiView (screw): common
- Daikin McQuay: screw and scroll across range
- Tecnoclima / specialty European: premium efficiency, limited US distribution
Common service mistakes
References
- ASHRAE Handbook - HVAC Systems and Equipment (chillers chapter)
- ASHRAE 90.1 (energy standard for buildings; chiller efficiency requirements)
- ASHRAE 188 (Legionellosis: Risk Management for Building Water Systems)
- AHRI 550/590 (chiller performance ratings)
- EPA Section 608 (refrigerant handling)
- Manufacturer service manuals (Trane, Carrier, York, Daikin McQuay)