Chiller Systems (Commercial) Reference

Why this matters

Commercial chillers are central air conditioning's bigger sibling - instead of cooling air directly, they cool water (chilled water at 42-45 °F supply) that's then circulated to air handlers throughout the building. They scale from 10 tons (small office) to 1000+ tons (high-rise). The diagnostic approach differs from split residential systems - chillers have more sub-systems (chilled water loop, condenser water loop, refrigerant circuit, controls, often multiple compressors), and a chiller failure can shut down an entire building's cooling.

Chiller architecture

Refrigerant circuit:

  • Compressor (centrifugal / screw / scroll / reciprocating, varies by tonnage)
  • Condenser (water-cooled or air-cooled)
  • Expansion valve (TXV or EEV)
  • Evaporator (cools the chilled water loop)

Chilled water loop:

  • Pumps circulate water through evaporator (where it's cooled)
  • Distributed to AHUs (air handler units) throughout the building
  • Returns warm to the chiller for re-cooling

Condenser water loop (water-cooled chillers only):

  • Pumps circulate water through condenser (where it picks up heat)
  • Routed to cooling tower (rejects heat to atmosphere via evaporation)
  • Returns to condenser

Air-cooled chillers skip the water condenser; instead, large condenser coils with fans reject heat directly to outdoor air. Simpler but less efficient and noisier.

Compressor types by tonnage

Type Tonnage range Characteristics
Reciprocating 5-200 tons Older, fewer in service; multiple cylinders; loud
Scroll 10-200 tons Quiet, reliable, smaller commercial; common in mid-sized buildings
Screw 50-500+ tons Twin-rotor compression; efficient at part-load; common large commercial
Centrifugal 200-2000+ tons Most efficient at full load; large building / chiller plants; impeller-based
Variable-speed inverter scaled Modern efficiency boost; magnetic bearings on premium units

Key performance metrics

  • Tonnage: 1 ton of cooling = 12,000 BTU/hr (the energy to melt 1 ton of ice in 24 hours)
  • kW/ton: electrical input per ton of cooling. Lower is better. Modern chillers: 0.45-0.55 kW/ton at full load; 0.35-0.50 at part-load IPLV.
  • IPLV (Integrated Part-Load Value): weighted-average efficiency across load profile; meaningful for buildings that run mostly part-load.
  • COP (Coefficient of Performance): cooling out / electricity in. Modern chillers: 5-7+ at full load.
  • ΔT chilled water: typical 10-12 °F (55 °F return - 44 °F supply, for example)
  • ΔT condenser water: typical 10 °F (85 °F supply - 95 °F return, for example)

Refrigerants in chillers

  • R-134a: common in centrifugal chillers; being phased down under HFC regulations
  • R-1234ze, R-513A: low-GWP replacements becoming common
  • R-410A: scroll chillers, packaged units
  • R-32: newer scroll units
  • Ammonia (R-717): industrial / very large; not residential
  • Always check the refrigerant type before service; EPA Section 608 cert required

Common failure modes

Chiller won't start / locks out on safety:

  • Low chilled-water flow → flow switch open
  • High discharge pressure (condenser water issue, cooling tower problem, refrigerant overcharge)
  • Low suction pressure (refrigerant undercharge, low chilled-water temperature)
  • Compressor overload
  • Microprocessor fault (read fault codes)

Chiller runs but doesn't cool to setpoint:

  • Refrigerant low → recover, leak-check, recharge
  • Condenser tubes scaled / dirty → reduced heat rejection → high discharge
  • Evaporator tubes scaled / dirty → reduced heat absorption → low chilled-water capacity
  • Compressor mechanical degradation → low compression ratio
  • Excess load → building demand exceeds chiller capacity

Chiller cycles rapidly:

  • Chilled water flow inadequate (short cycling on flow switch)
  • Setpoint too tight
  • Pump issues

Cooling tower issues (water-cooled):

  • Fan failure → no heat rejection
  • Spray nozzles plugged → low water flow over fill
  • Bleed-off valve clogged → high TDS in water → scale formation
  • Belt drive worn → fan slow

Maintenance schedules (industry-standard)

Daily / weekly:

  • Read pressures, temperatures, water flows
  • Log chiller status
  • Check cooling tower water quality (TDS, pH)
  • Verify normal operation

Monthly:

  • Clean cooling tower strainer
  • Check chilled water and condenser water pH, biocide levels
  • Inspect for visible leaks
  • Verify control sequence

Quarterly:

  • Check refrigerant charge (subcool / superheat) - see Superheat Subcooling Method Reference
  • Test safety controls (high-pressure cutout, low-pressure cutout, freeze stat)
  • Inspect electrical connections in starter

Annually:

  • Eddy-current testing of chiller tubes (every 3-5 years)
  • Condenser water chemistry full analysis
  • Refrigerant leak test (per EPA 608)
  • Compressor oil analysis
  • Bearing lubrication / replacement per manufacturer

Water quality (water-cooled chillers)

Cooling tower water is exposed to air and concentrates impurities as water evaporates. Without treatment:

  • Scale formation: calcium carbonate deposits on condenser tubes; thermal resistance climbs; chiller efficiency drops
  • Biological growth: algae, bacteria (including Legionella) thrive in warm, oxygenated water
  • Corrosion: dissolved oxygen + dissolved minerals attack metal components

Treatment program:

  • Conductivity-based bleed-off (controls TDS / cycles of concentration; typical 3-5 cycles)
  • Corrosion inhibitor
  • Scale inhibitor / dispersant
  • Biocide (oxidizing + non-oxidizing rotation)
  • Routine testing (weekly or biweekly)
  • Annual Legionella testing per ASHRAE 188 in some applications

Brand-specific notes

  • Trane CenTraVac (centrifugal): premium, common large commercial; Magnetic Bearing chillers (no oil) on newer Series E units
  • Carrier 19XR / 23XR (centrifugal): premium large
  • York Millennium / OptiView (screw): common
  • Daikin McQuay: screw and scroll across range
  • Tecnoclima / specialty European: premium efficiency, limited US distribution

Common service mistakes

References

  • ASHRAE Handbook - HVAC Systems and Equipment (chillers chapter)
  • ASHRAE 90.1 (energy standard for buildings; chiller efficiency requirements)
  • ASHRAE 188 (Legionellosis: Risk Management for Building Water Systems)
  • AHRI 550/590 (chiller performance ratings)
  • EPA Section 608 (refrigerant handling)
  • Manufacturer service manuals (Trane, Carrier, York, Daikin McQuay)