Indoor Air Quality Testing + Diagnostics
Why this matters
The IAQ sales conversation closes when the tech can SHOW the customer their problem with a number - particulate count, CO2 level, mold spore reading, CO concentration. Without measurement, "I think you have a dust problem" is a guess; with measurement, "your living room PM2.5 is 38 µg/m³ - that's 5x the EPA daily standard" is a diagnosis. IAQ testing is the proof step that converts the IAQ recommendation from suggestion into prescription.
The measurable IAQ parameters
Particulate (PM2.5, PM10)
- PM2.5: fine particles ≤ 2.5 µm - wildfire smoke, combustion, vehicle exhaust, fine dust
- PM10: particles ≤ 10 µm - coarse dust, pollen, mold fragments
- EPA standards: PM2.5 daily 35 µg/m³, annual 12 µg/m³; PM10 daily 150 µg/m³
- Health concern: PM2.5 penetrates deep into lungs, linked to cardiovascular + respiratory disease
Carbon Dioxide (CO2)
- Outdoor ambient: 420 ppm (2025)
- Acceptable indoor: < 1,000 ppm
- ASHRAE target: ≤ 1,000 ppm increment over outdoor
- Drowsiness/headache: 1,000 - 2,000 ppm
- Severe: > 5,000 ppm
- CO2 is the proxy for ventilation adequacy - high CO2 = inadequate fresh air
Carbon Monoxide (CO)
- 0 ppm baseline
- < 9 ppm acceptable (residential ASHRAE)
- 9 - 35 ppm - investigate combustion sources
-
35 ppm - DANGER; evacuate + investigate immediately
- CO alarms must alarm at ≥ 70 ppm for 1 hr OR ≥ 150 ppm for 10 min
Volatile Organic Compounds (TVOC)
- < 250 ppb (parts per billion) ideal
- 250 - 500 ppb - acceptable
-
500 ppb - investigate source (paint, cleaning products, off-gassing)
-
2,000 ppb - major concern
Humidity
- 30 - 60% relative humidity ideal
- < 30% - dry skin, static, mucous membrane irritation
-
60% - mold growth + dust mite proliferation
-
70% - major mold concern
Mold spores (CFU per cubic meter or per gram)
- Air vs surface samples; lab analysis required
- Result interpretation requires comparison to outdoor baseline
- Indoor / outdoor ratio of 1 - 2x normal; > 5x suggests indoor source
Radon
- < 2 pCi/L acceptable (EPA action level 4 pCi/L)
-
4 pCi/L - mitigation recommended
- Long-term (90 day+) tests vs short-term (3 - 7 day) - long-term more reliable
- See Radon Mitigation Basics
Testing tools
- Multi-gas IAQ meter: PM2.5/PM10 (laser scattering), CO2 (NDIR), CO (electrochemical), VOC (PID/MOS), temp + RH. Brands: Aeroqual, TSI Q-Trak, AirAdvice, IQAir AirVisual. Prosumer: PurpleAir, Awair, Foobot.
- Anemometer: verify ventilation rates + test supply/return balance.
- Particle counter: lab-grade 6-channel (0.3 - 10 µm); verify HEPA + MERV capture.
- Manometer: differential pressure across filters + heat exchangers; house pressure balance.
- Radon test kit: short-term 3 - 7 day or long-term 90 day alpha-track; EPA-certified lab.
On-site testing protocol
Initial assessment (30 - 60 min): customer interview (symptoms, season, renovations, pets, smokers); visual walk-thru (mold, moisture damage, dust, current filter); HVAC inspection (filter age, ductwork, returns/supplies); combustion appliance inventory.
Multi-point IAQ testing (1 - 2 hr): outdoor baseline at a screened location, then living room (occupied breathing height), master bedroom, kitchen (during cooking if possible), basement/utility, near each combustion appliance for CO specifically. Document readings + time + location.
Source isolation: high particulate (cooking spike? pets? filter?), high CO2 (ventilation inadequate), high VOC (paint, cleaning, off-gassing), high CO (combustion analysis immediately), high humidity (crawlspace, bath vent, cooking).
Report: tabulated readings vs reference levels, photos of HVAC + combustion sources, specific recommendations with cost ranges.
Mold-specific protocol
Suspect mold:
- Visible discoloration on wall, ceiling, floor (verify it's mold + not just dirt)
- Musty odor
- Customer complaints: allergy, respiratory, neurological symptoms
Air sampling:
- Outdoor sample (control)
- Indoor sample in suspect rooms
- Calibrated pump @ 15 L/min for 5 min per sample
- Bring samples to certified mold lab
- Lab returns species + CFU count
- Compare indoor vs outdoor; indoor > 5x outdoor of same species = indoor source
Surface sampling (when visible mold present):
- Tape lift or swab onto sterile media
- Lab identifies species
Limitations of mold testing:
- Single sample is a snapshot; spore counts vary hour-by-hour
- A clean sample doesn't rule out mold (intermittent exposure)
- Visual + moisture inspection + air sample together = diagnosis
- Most contractors are NOT mold remediation contractors; if confirmed, refer to licensed remediator + don't disturb the area
Combustion back-drafting test
Combustion appliances back-draft when combustion air supply is inadequate, house pressure is negative from exhaust fans/dryer, vent is blocked, draft inducer failed, or venting improper. Test: close all windows + doors, turn on all exhaust (bath, kitchen, dryer), measure house pressure (should not exceed -3 Pa), light each combustion appliance + observe vent draft 10 min, CO test (< 100 PPM in flue, < 9 PPM at face). Mitigate with combustion air, sealed appliances, makeup air fan, or removing offending exhaust.
Specialists + reporting
Refer out: asbestos (licensed abatement), lead paint (RRP contractor), mold remediation > 10 sq ft (licensed remediator), radon mitigation (certified), sewer gas (plumber), VOC ID (industrial hygienist). Customer reports that close: one-page summary with traffic-light per parameter, specific finding per red/yellow item, recommendation with cost range, clear next step. The report is a sales document, not a science paper.
References
- ASHRAE 62.1 + 62.2 (Ventilation for Acceptable Indoor Air Quality)
- EPA Indoor Air Quality reference levels
- AIHA + ACGIH industrial hygiene guidance
- NIOSH Pocket Guide to Chemical Hazards
- Manuall internal: Indoor Air Quality Services, Indoor Air Quality ERV HRV