Generator Fuel Options Reference
Overview
The fuel decision determines cost per kWh, run duration, refueling logistics, + storage hazards. For standby generators, fuel choice is typically natural gas or propane; for portable, also gasoline or diesel. This reference covers trade-offs.
Natural gas (most common standby)
Pros
- Continuous supply (utility pipeline; no refueling)
- Lower cost per BTU than propane
- Indefinite runtime
- No fuel storage on-site
- No fuel spills
- No fuel theft
Cons
- Subject to utility outage (rare, but earthquakes, gas line damage)
- Requires gas pipeline at property
- Slightly lower power density than gasoline/diesel
- Pressure drop concerns with high gas demand (verify meter sizing)
Best for:
- Suburban homes connected to natural gas
- Permanent installations
- Customers wanting "set it and forget it"
Cost (2025):
- Natural gas: (100,000 BTU)
- Generator at full load: ~ of run time
Propane (second most common standby)
Pros
- Higher power density than natural gas
- Can be stored on-site (no utility dependency)
- Works in rural areas
- Cleaner burn than gasoline/diesel
- Long shelf life (no degradation like gasoline)
Cons
- Tank required (storage + space)
- Refilling costs + scheduling
- Tank monitoring required
- Vapor pressure drops in extreme cold (under -10°F gradually)
- Initial tank cost
Best for:
- Rural / no natural gas service
- Customers wanting fuel independence
Tank sizing:
| Tank size | Backup capacity (22kW gen full load) |
|---|---|
| 100 gal | ~30 hours |
| 250 gal | ~80 hours |
| 500 gal | ~170 hours |
| 1,000 gal | ~330 hours |
For a typical home + 22kW generator: 500-gallon tank gives roughly 1 week of runtime. Adjust for actual load + outage duration concerns.
Cost (2025):
- Propane:
- Generator at full load: ~
- Annual filling cost (if used):
Gasoline (portable generators)
Pros
- Widely available (any gas station)
- Cheap fuel
- Easy to handle small quantities
Cons
- Limited shelf life (3-6 months without stabilizer; 1-2 years with)
- Flammable + explosive risk
- Theft concern
- Refueling required during outage
- Carburetor gumming if not maintained
Best for:
- Portable generators
- Short-duration outages
- Customers who can refuel during outage
Storage:
- Approved fuel cans (5 gallon max)
- Vented, cool location
- Away from ignition sources
- Fresh fuel only (stabilizer recommended)
- Code limits typical: 25 gallons in residential garage; varies by jurisdiction
Cost (2025):
- Gasoline:
- 5kW portable at full load: ~
Diesel (commercial + large residential)
Pros
- Highest energy density (longest runtime per gallon)
- Long fuel storage life (with treatment)
- Reliable in cold weather
- Heavy-duty engine (longer lifespan)
Cons
- Most expensive fuel
- Smelly + noisy operation
- Particulate emissions higher
- Diesel engines more expensive to maintain
- Less common in residential
Best for:
- Large estates
- Mission-critical applications (medical equipment, server rooms)
- Locations without natural gas + budget for premium
Cost (2025):
- Diesel:
- Large generator (50kW) full load: ~
Dual-fuel options
Some generators accept multiple fuels:
- Tri-fuel (gas, propane, natural gas): portable + commercial
- Dual-fuel (gasoline + propane): common portable upgrade
- Convertible: natural gas + propane (standby with conversion kit)
Pros:
- Fuel flexibility
- Backup option if primary unavailable
Cons:
- More complex carburetion
- Slightly more expensive
- Different output ratings per fuel type
Fuel pressure requirements (gaseous)
Natural gas:
- Most generators: 7-11 inches water column (low pressure)
- Some commercial: 1-2 PSI
- Generator manufacturer specifies; check supply pressure
Propane:
- 11-14 inches water column (slightly higher than natural gas)
- Regulator at tank provides correct pressure
Important: if pressure too low, generator runs lean (worse emissions, won't hit full power); too high, generator runs rich (carbon buildup, fouled spark plugs).
Fuel line sizing
For natural gas runs:
- 1/2" pipe: ≤ 5 ft, up to 14 kW
- 3/4" pipe: ≤ 25 ft, up to 22 kW
- 1" pipe: ≤ 50 ft, up to 30 kW
- 1-1/4" pipe: longer runs or larger generators
For propane: similar but verify with manufacturer specs.
Plumber should verify pressure at generator under full-load conditions.
Code + regulatory
Local codes:
- NFPA 54 (Natural Gas Code)
- NFPA 58 (Liquefied Petroleum Gas Code)
- IFGC (International Fuel Gas Code)
- Local amendments
Permits: gas permit + electrical permit + sometimes building permit
Inspection: pressure test + leak check + permit closeout
Tank placement (propane)
Code-required distances:
- 10 ft from home (some areas)
- 10 ft from property line
- 25 ft from ignition sources
Local code varies; verify before placement.
Refilling logistics (propane)
- Local propane supplier provides scheduled refills
- "Keep full" service: supplier monitors, refills when 30% remaining
- Customer pays per delivery or per gallon
- Some suppliers offer remote monitoring + automatic refill
When to recommend each fuel
Recommend natural gas:
- Utility service available
- Customer wants no fuel management
- Indefinite runtime priority
Recommend propane:
- Rural / no natural gas
- Customer wants fuel independence
- Outage frequency high
Recommend gasoline (portable only):
- Short-duration outages
- Customer comfortable with refueling
- Lower budget
Recommend diesel:
- Very large loads
- Mission-critical (medical, business)
- Large fuel storage acceptable
Fuel system maintenance
For each fuel:
- Natural gas: annual inspection of supply line + pressure regulator
- Propane: tank inspection annually; regulator every 10 years
- Gasoline: drain + replace fuel every 6 months OR use stabilizer
- Diesel: water + sediment removal; fuel polishing for long-storage
The single biggest fuel-decision factor most customers don't think about: REFUELING DURING AN OUTAGE. If a winter storm knocks out power for 5 days, gasoline stations may also be out of power (no gas to dispense). Natural gas + propane don't have this problem. For mission-critical preparedness, fuel that DOESN'T depend on commercial activity is the right choice - natural gas or propane.
References
- NFPA 54, 58, 110
- IFGC (International Fuel Gas Code)
- Manufacturer fuel pressure specifications
- Manuall internal: Generator Sizing for Residential, Whole-House Standby Generator Installation SOP